We are counted amongst the prominent entities, engrossed in manufacturing and exporting technologically advanced CNG Gas Detection System that is widely used to detect highly combustible gas that is CNG. This detection system is manufactured by our deft professionals using quality components and latest technology in sync with the set ISO norms. Clients can avail this CNG Gas Detection System from us in different technical specifications as per their requirements at reasonable prices.

Features:

  • Gas leakage is monitored during power failure or other life line failures (on models with a built-in back up power supply).
  • Constantly monitors for 30 minutes after a power failure and then erratically monitors for 2 days, the intermission between observations depends on the number of detection points. (NV-400)
  • Tested normally in a seismic qualification test equal to intensity of 7 on the Japanese earthquakes.
  • A Plastic molded case which contains the electronic circuit is hard to break and has substantially improved insulation; the case structure has been refined to increase the strength.
  • Shows gas concentration at the time of an alarm as a glance.
  • Battery life can be measured by one-touch operation. (Battery life check function)
  • Very easy to change the alarm set value. (Δ‡ key)
  • Wide operating voltage range of 85-264V.

Technical Data 

Item / Model

NV-400

Detection Principle

Hot Air Semiconducter

Gas Detected

NV-400 : Town gas (Natural gas)

Detection Points per Unit

Monitors 2 points per unit

Detection Range

NV-400 : 0-100%LEL

Concentration Indicator
Alarm Set Value Indication
Backlight
Peak Hold Function (on alarm)

LCD bar-graph meter (53 dots x 2 lines)
Direct reading scale
Yes
Holds a peak value on alarm, which is canceled by the reset

Alarm Set Value (default value)

NV-400: 10%LEL fir Ist stage, 24%LEL for 2nd stage

Alarm Accuracy

±25% of an Alarm Set Value (under identical conditions)

Response Time

NV-400: 30s or less at 160% concentration of an Alarm Set Value (excluding sampling delay for suction type)

Alarm Indication

Individual Alarm Lamp
Self-holding type

On Alarm : Flashes red, lights up after the Buzzer Stop Complete lock (Turn off by the reset after the level declined)

Alarm Sound

On Alarm : Intermittent buzzer, stops after the Buzzer Stop

External Alarm Output

Individual Alarm Contact

1 a no-voltage (Contact capacity : 2A@100V AC)

Individual Voltage output

0-6-12V DC (20,A or Less)

Collective Alarm Contact

1 c no-voltage (Contact capacity : 2A@100V AC)

Centralized Monitor Panel Output

0-6-12V DC (20,A or Less)

External Buzzer Contact

1 a no-voltage (Contact capacity : 2A@100V AC)

External Buzzer Voltage
Output

Intermittent voltage signal (12V DC, 10mA or less)

Alarm Delay

Selectable by a DIP awitch (10s constant)

Main power Source

85-264V AC

Power Consumption

When Using KD-5

Diffusion type (15+3.5n)VA

When Using PE-2DC

Suction type (15+7.5n)VA

Backup Power Source (Only on models with a built-in backup power supply)

Battery Type

Sealed Lead Acid Battery

Overdischarge Prevention Function

Yes

Battery Life Check Function

Yes

Battery Viltage indication

2-digit LED

exterior Color

Munsell 2.5PB 7.0/1.0